Problem: Cal Y Motor Failure
Manifestation:
In Shane AO motor control GUI:
-
Motor fails to move, ceases moving, fails to calibrate or acheive
commanded position.
-
Detail panel reports off-on-error message.
-
In detail panel, CALYRAW value does not change.
-
In detail panel, CALYGTE achieves a value of 1000.
-
No indication that motor is moving.
Solution/Recovery:
-
Cal Y motor corresponds to Galil 2, stage F (saomot2).
Intervention:
If attempts at above solution/recovery are unsuccessful.
-
Locate, inspect re-seat cables/connections to Galil.
-
Attempt re-calibration of function.
-
If continued failure:
user@shred.ucolick.org > ao restart saomot2
Then, re-attempt re-calibration of function.
-
Consider lubricating motor stage and/or associated limit switches.
Cause:
-
Loose connection (of little card attached to Galil for I/O).
Attachment screws not engaged securely.
Large cable loom in physical contact with this component.
-
Possible binding of motor stage and/or associated limit switches.
Associated Issues:
Change Log:
- 2017-08-05: Updated (binding/lubrication of limit switches).
- 2016-12-15: First version.
|